XM31-915-HP - 10087456
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 41.15 V
Battery Balancing Balancing
Balancing String String A
Battery System Configuration 2 strings of 3 batteries each
Battery Temperature 22 °C
72 °F
  1 2 3 Balancing
String A 13.86 V 13.80 V 13.74 V Moderate
String B 13.77 V 13.77 V 13.83 V Moderate
Battery Charging
Charger Mode Float
Current Charger Mode Time 5,694 min
Charger Current 0.00 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model Other
Accept Voltage 2.40 V/cell
Float Voltage 2.27 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 100 Ah
Temperature Compensation 5.00 mV/cell/°C
HP Battery Rest Mode No
Battery String Detect Auto
Number of Battery Strings 2
Heater Mat Installed No
Conductance
Last Conductance Measurement  
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 0 S(℧)  
String A Battery 2 0 S(℧)  
String A Battery 3 0 S(℧)  
String B Battery 1 No value available S(℧)  
String B Battery 2 No value available S(℧)  
String B Battery 3 No value available S(℧)  

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.
www.alpha.com   |   www.enersys.com